Air Circuit Breakers ME10
12
Reference guide - October 2014
Electronic Trip Units
LT protection
ST protection
Measurement
Diagnostic
GF protection
GT-Rating Plug
LT protection
ST protection
Canale I
Measurement
Diagnostic
GF protection
I extended protection
Modbus
GT-Rating Plug
LT protection
ST protection
I protection
RELT
Measurament
2
Diagnostic
Input/Output
GF protection
I extended protection
ZSI
Modbus
GT-Rating Plug
Description
Overload current setting Ir=0,2… 1In
Class C 0,5... 40
Neutral protection (50%-63%-100%)
Thermal memory
Short-circuit setting 1,5… 12Ir
Time delay adjustable 30... 940ms
I
2
t protection time bands available
Current L1, L2, L3
Trip reason indication
Trip counter
Event logger
Watchdog
Ground fault setting 0,1… 1In
Time delay adjustable 30... 840ms
I
2
t protection time bands available
(required for all types)
Overload current setting Ir=0,2… 1In
Class C 0,5... 40
Neutral protection (50%-63%-100%)
Thermal memory
Short-circuit setting 1,5… 12Ir
Time delay adjustable 30... 940ms
I
2
t protection time bands available
Istantaneous short circuit setting 2… 15Ie
Selective execution
Fixed istantaneous or HSOC protection
Current L1, L2, L3
Trip reason indication
Trip counter
Event logger
Watchdog
Ground fault setting 0,1… 1In
Time delay adjustable 30... 840ms
I
2
t protection time bands available
Istantaneous short circuit setting 2…30Ie
Modbus communication
(required for all types)
Sovraccarico Ir=0,2…1In
Class C 0,5... 40
Neutral protection (50%-63%-100%)
Thermal memory
Short-circuit setting 1,5… 12Ir
Time delay adjustable 30... 940ms
I
2
t protection time bands available
Istantaneous short circuit setting 2… 15Ie
Selective execution
Fixed istantaneous or HSOC protection
Istantaneous 40ms
Current L1, L2, L3
Voltage L1, L2, L3
Energy (kWh)
Real, apparent, reactive, total power
Peak and demand power
Frequency
Trip reason indication
Trip counter
Event logger
Watchdog
2 electronic inputs
2 general relay outputs
Ground fault setting 0,1… 1In
Time delay adjustable 30... 840ms
I
2
t protection time bands available
Istantaneous short circuit setting 2… 30Ie
Zone selective interlock
Modbus communication
(required for all types)
Catalogue
number
GTG00K1-SF
1
GTG00K2-SR
GTPUNI
GTG00K9-SF
1
GTG00K4-2SR
GTPUNI
GTG00K9-4SF
1
GTG00K4T6SR
GTPUNI
Reference
number
408800
408802
408860
408803
408809
408860
408813
408819
408860
GT-E
GT-S
GT-N
+
+
+