UPS OPERATING INSTRUCTIONSPROTECT 1.100 PROTECT 1.150PROTECT 1.200PROTECT 1.

Página 2

10Parallel system with PROTECT 1.150Number of UPS unitsAvailable power1 2 30 15 kVA 30 kVA 45 kVA1 --- 15 kVA 30 kVAActiveredundancydegree2 --- --- 15

Página 3 - Instructions

112.3 Technical DataType ratingPROTECT 1.100 10000 VA (cos ϕ = 0.7 ind.)7000 W PROTECT 1.150 15000 VA (cos ϕ = 0.7 ind.) 10500 WPROTECT 1.200 20000 VA

Página 4 - Copyright

12Overload behaviour Up to 105% continuous;with mains supply > 105% – < 130% for 10 min.130% for 1sFollowing this, automatic, uninterrupted swit

Página 5 - Table of Contents

13CommunicationInterfaces RS232Sub-D (9-pin)Additionally: Communication slot for expansions (e.g. AS/400 / USB / remote signal indicator /SNMP, …)Shut

Página 6

14Housing colour: BlacklineWeight:PROTECT 1. 100 39 kgPROTECT 1. 150 55 kgPROTECT 1. 200 55 kgPROTECT 1. 100 BP 135 kgPROTECT 1. BP20 170 kgDimensions

Página 7 - 2 General Information

153 Safety Regulations3.1 Important Instructions and ExplanationsThe instructions for operation and maintenance, as well as the following sa

Página 8 - 2.2 System Description

16♦ Verify that the unit is disconnected from the power supply♦ Earth and short-circuit the unit♦ Provide protection by covers or barriers for any nei

Página 9

17For health and safety reasons, the unit must be earthed correctly!The PROTECT 1. may only be operated with or connected toa three-phase power

Página 10

18♦ Ensure that no fluids or foreign bodies can penetrate the housing!♦ Do not block the air vents of the unit! Make sure, for example, that children

Página 11 - 2.3 Technical Data

19Therefore, take the following safety precautions when working with batteries:♦ Take off watches, rings and other metallic objects! ♦ Only use tools

Página 12

2Thank you for deciding to purchase the PROTECT 1. UPSfrom AEG Power Solutions. The following safety instructions are an important part of the operat

Página 13

203.5 CE Certificate

Página 14

214 Set-up4.1 Unpacking and InspectionThe unit has been completely checked and inspected. Although the unit has been packed and shipped

Página 15 - 3 Safety Regulations

22Please keep plastic packaging bags away from babies and children in order to safeguard against suffocation accidents.Handle the components with care

Página 16 - 3.3 Qualified Personnel

234.3 Set-UpNote the following points when setting up the UPS system and its external battery units (special accessories):♦ The contact surfa

Página 17

244.4 Overview: Connections, Operating / Display Elements4.4.1 Front viewPROTECT 1.100 PROTECT 1.150 PROTECT 1.200PROTECT 1.100BP PROTECT 1.BP20

Página 18

254.4.2 Display1. OFF pushbutton2. ON pushbutton / alarm off3. Orange-coloured Bypass LED4. Green Inverter LED5. Orange-coloured Battery LED6. Green L

Página 19

264.4.3 Rear view (connections):PROTECT 1.100PROTECT 1.150 / 1.20012345678N L1 L2 L3 JP1 JP2 L N1.1 1.2 1.3111391011412356687N L1

Página 20 - 3.5 CE Certificate

27Explanations:1. Connection terminal cover for mains/UPS input (1.1) and output (1.3), additional pair of terminals for setting individual or paralle

Página 21 - 4 Set-up

285 Electrical ConnectionCautionPrior to commencing work, ensure that the connection cables are de-energised and that it is not possible to acti

Página 22

295.1 Safety of PersonnelNote the following points when setting up the UPS system and its external battery units (special accessories):♦ Disc

Página 23 - 4.3 Set-Up

31 Notes on these Operating InstructionsDuty to provide informationThese operating instructions will help you to install and operate the Unint

Página 24 - Elements

30♦ Mechanically secure the cables with the strain relief clamps of the cable clamping unit.♦ Mount the connection cover of the cable clamping unit.5.

Página 25

31Alternatively, the 10 kVA UPS system can also be connected via a multi-wire rubber-sheathed cable.5.4 Mains Connection5.4.1 Preparation for the thre

Página 26 - PROTECT 1.100

32♦ Place the “maintenance switch” manual bypass on the back of the UPS in the “bypass” position. To do this, firstremove the 4 screws of the cover (n

Página 27

335.4.4 Connection of the LoadsIn order to ensure the safety of personnel during installation work, make sure that the connections are

Página 28 - 5 Electrical Connection

345.5.1 Connection of the Battery Cubicle PROTECT 1.100 BPThis battery cubicle is completely preconfigured. The connection to the UPS unit

Página 29 - 5.1 Safety of Personnel

355.5.2 Connection of the Battery Cubicle PROTECT 1. BP20Fig.: Rear view of the PROTECT 1.BP20 with cover removed.The battery cubicle is supplied with

Página 30

36If the battery cubicle is used in connection with the PROTECT 1.1.50 or PROTECT 1.200, the strain relief is implemented with clamps.

Página 31 - 5.4 Mains Connection

376 Start-UpCompare the setting of the nominal output voltage of the UPS with the rated voltage valid in your country. The factory presetting

Página 32

38iPlease shut down the entire system again if you cannot solve a problem that occurs. To do this, press the OFF pushbutton for approx. 2 secon

Página 33 - 1.100 BP

39continuously supplied with reliable and “clean” voltage with no interruptions in this operating mode.The bar graph LED (LED chain above the

Página 34

4liability for consequential damage. AEG will rescind all obligations such as warranty agreements, service contracts, etc. entered into

Página 35

40The inverter is switched off if the battery voltage drops below a factory-set minimum voltage value. Never store the unit in this condition! The dis

Página 36

41This so-called passive redundancy protects against the total failure of the voltage supply on the secured busbar; however, in this operating mode

Página 37 - 6 Start-Up

42The manual bypass enables maintenance and service personnel to perform work on the PROTECT 1. without having to switch off the load ci

Página 38 - 6.1 Operating Modes

437 Interfaces and Communication7.1 Computer Interface RS232For the control of the UPS and convenient reading of status messages and measur

Página 39

44The "CompuWatch" shutdown software supports different operating systems, e.g. Windows 98SE/ME, Windows NT/2000/XP, Windows Vista

Página 40

458 Displays and Troubleshooting8.1.1 Signalling1. OFF pushbutton Press the button for approx. 2 seconds to switch off the UPS.2. ON button: Pre

Página 41

466. Line LED (mains status): The green LED lights up when the mains voltage present is within the specified tolerance range. If this LED flashes, eit

Página 42

478.1.2 Overview Table of LED Displays / Acoustic Warning SignalsLED display (see chapter 8 on page 47)No. Operating modeWarning signal10% – 35%utilis

Página 43 - 7.2 Communication Slot

48Overview table of LED displays / warning signals, cont.LED display (see chapter 8 on page 47) No. Operating modeWarning signal19Short-circuit output

Página 44

498.2 FaultsPROTECT 1. outputs detailed error messages by means of which you or the service personnel can quickly and accurately localise and

Página 45

5Table of Contents1 Notes on these Operating Instructions ...32 General Information ...

Página 46

50Message / display Cause SolutionDuration of the emergency power supply shorter than setpoint.Batteries not completely charged / batteries aged or fa

Página 47 - Warning

519 Parallel Operation9.1 Principle of OperationPROTECT 1. has been designed for parallel operation with n+x technology (“n” here stands for the numbe

Página 48

52The actively redundant parallel operation automatically switches to power-increasing operation if the output power requirement exceeds

Página 49 - 8.2 Faults

53communication of the units switched in parallel takes place via the 25-pin parallel operation cable(s) included in the scope of delivery.For

Página 50

54each UPS are in the “Bypass” position and all mains input miniature circuit breakers (no. 2, p. 26/27) on the back of each UPS are in the

Página 51 - 9 Parallel Operation

557. Now actuate the mains input miniature circuit breakers(no. 2, p. 26/27) on each UPS one after the other.Move them to the "ON" po

Página 52

5611. When the displays are lit as described, switch onyour loads one after the other. When doing this, take care not to exceed the maxi

Página 53

5710 MaintenanceThe PROTECT 1. consists of state-of-the-art, non-wearing components. We do, however, recommend visual checks (above all ba

Página 54

58CAUTION! PROTECT 1. must be disconnected from the power supply prior to carrying out the following work.If large quantities of dust have accumulated

Página 55

5911 Storage, Dismantling and Disposal11.1 StorageLong storage times without charging or discharging the battery at regular intervals may l

Página 56

66 Start-Up...376.1 Operating Modes ...

Página 57 - 10 Maintenance

6012 List of Terms12.1 Technical terminologyDC/DC booster Circuit technology for increasing a DC voltage to a higher voltage levelSBS Static Bypass Sw

Página 58

61Guarantee CertificateType: …….…………………...Unit number: ………….……………...

Página 59 - 11.3 Disposal

72 General Information2.1 TechnologyiPROTECT 1. is an Uninterruptible PowerSupply (UPS) for essential loads such as small data centres, servers,

Página 60 - 12 List of Terms

82.2 System DescriptionThe UPS is connected between the public utility mains and the loads to be protected.The power section of the rectifier c

Página 61 - Guarantee Certificate

9IGBT power semiconductors of the inverter, a voltage system of the highest quality and availability on the secured busbar.In the event of mains fault